CF-C3502
Fire alarm control panel with 2 zones
Attractive surface or recessed mounting
Zone disablements
- Comprehensive range of engineering functions
- Ability to differentiate between Manual Call Point or automatic detector alarm
- Programmable sounders for automatic and/or manual activation 72 hour standby as standard
| Power Supply Mains | 100V-240V ac |
|---|---|
| Integral Charger | 600mA |
| Auxiliary 24V output | 24V dc, max 150mA |
| Mains Fuse | 16A time delay (not replaceable) |
| Battery Fuse | 1.6A resettable fuse |
| Working Voltage | 18V to 30V DC |
| Current Consumption | 22mA (24V DC) + Zone Load |
| Number of Detector Zones | 2 |
| Max Zone Cable Length | 500 m |
| Max Zone Cable Capacitance | 0.25µF |
| Max Zone Cable Resistance | 15Ω per conductor |
| Detector Circuit EOL Values | Resistive(8.2Ω) or capacitive (100µF+22Ω) |
| Max Quiescent Zone Load | 5mA per zone |
| Max Number of Detectors | 25 per zone (smoke or heat) |
| Maximum Number of Devices | 32 (MCP and Dets) per zone |
| MCP Series Resistor Values | 180Ω ±5% |
| Number of Alarm Circuits | 2 |
| Alarm Circuits EOL Value | 10kΩ ±5% ¼W |
| Maximum Alarm Load | 400mA per circuit |
| Class Change Input | Activates alarm outputs |
| Global Fault Contacts | 24V DC 1 A rating |
| Global Fire Contacts | 24V DC 1 A rating |
| Temperature Range | -5 to 40°C |
| Humidity Limit | 95% RH, Non-Condensing |